TITAN Intended use Valid for all application diagrams Example 3 The following sash is to be fitted with hardware according to the associated application diagram: • Intended sash rebate width (FFB) = 1.300 mm • Intended sash rebate height (FFH) = 1.800 mm • Intended glazing 3 x 4 mm float glass – GG = 30 kg/m2 Basis of testing and calculation: Tilt-turn test according to QM 328 Appendix 2–Figure A • 15.000 tilt & turn cycles • 10.000 turn cycle Additional loads taken into account in accordance with EN 14608 (Figure A.1)/Class 4 in accordance with EN 13115 (800 N) Requirements for the use of the application diagram: Proof that the load bearing components have been fixed to the window system by the window manufacturer in accordance with TBDK using the following forces: • To the top hinge with 2.710 N • To the bottom hinge with 2.890 N Comply with the following values for all window systems: • Max. width-to-height ratio QB/H ≤ 2,0 • Reduction in glass size CG ≥ 28 mm • Profile weight PG ≤ 3,25 kg/m2 GG kg/m2 S 50 500 3000 2500 2000 1500 1000 500 20 1000 1500 2000 FFH / FH mm FFB / FB mm 30 40 60 70 Result after reading the data in the application diagram: • The point of intersection (S) for FFB x FFH = 1.300 x 1.800 mm is to the left of the curve in the permissible range for the specific element weight GG = 30 kg/m2. • The hardware can be used as indicated in the associated application diagram. H58.AWD_BG_EN 03.2014 Page 7/11